Expansion modules for TROL
Trol I/O Expansion Module Power Requirements
115VAC .02A, 50/60Hz w/1000v magnetic isolation (I/O blocks are also available in 230vac or 12-24 vdc)
Outputs
4 normally open relay contacts unprotected, no leakage current 5Amps 230VAC (resistive load), 250 VA (inductive load)
Response time:
10ms operate / 5ms release
Rated life: 5 million (mech) / 200,000 3A (resistive load)
Inputs
6 self powered, 12-14 VDC 10ma. w/ 1000v optical isolation Maximum leakage of input device: 0.5ma Response time: all are factory set at 10ms, the user may change any input to between 0 to 255ms using the Setup
Physical
Size 2.9 (75mm) x 2.2(55mm) x 4.3 (110 mm)
Mounting DIN rail or panel
Weight 10 oz. (284 grams)
Temp 0 - 140 F, (no condensation)
Origin Designed and assembled in the USA.