Trol I/O Expantion blocks by Trol Systems

Air-Oil Systems

Manufacturer: Trol Systems

Part No. 6/4-20-115, 6/4-30-115, 6/4-40-115, 6/4-50-115, 6/4-60-115 and 6/4-70-115

Power Requirements
115VAC @ .02A, 50/60Hz w/1000v magnetic isolation
(I/O blocks are also available in 230vac or 12-24 vdc)
Outputs
4 normally open relay contacts unprotected, no leakage current
5Amps @ 230VAC (resistive load), 250 VA (inductive load)
Response time: 10ms operate / 5ms release
Rated life: 5 million (mech) / 200,000 @ 3A (resistive load)
Inputs
6 self powered, 12-14 VDC @ 10ma. w/ 1000v optical isolation
Maximum leakage of input device: 0.5ma
Response time: all are factory set at 10ms, the user may change
any input to between 0 to 255ms using the Setup Menu
Physical
Size 2.9" (75mm) x 2.2" (55mm) x 4.3" (110 mm)
Mounting DIN rail or panel (with two #6 screws)
Weight 10 oz. (284 grams)
Temp 0 - 140° F, 90% r. humidity (no condensation)
Origin Designed and assembled in the USA